EasyManua.ls Logo

Emerson 1420 - Functional Specifications; Input Power; Poe; Current Draw

Emerson 1420
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specifications and Reference Data
Reference Manual
00809-0200-4420, Rev HC
Appendix A: Specifications and Reference Data
July 2015
55
Appendix A Specifications and Reference
Data
Functional specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 55
Physical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 55
Communication specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 56
Self-organizing network specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 56
System security specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 56
Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 57
Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 59
Accessories and spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 60
A.1 Functional specifications
A.1.1 Input power
10.5 – 30 VDC (must be a Class 2 power supply)
A.1.2 PoE
(1)
Input voltage
Normal Operation (no PSE or IEEE 802.3af): 10.5 – 30 VDC
PoE + PSE Operation (IEEE 802.3at): 17.5 – 30 VDC
A.1.3 Current draw
Operating current draw is based on 3.6 Watts power
consumption.
Momentary startup current draw up to twice operating
current draw.
A.1.4 Radio frequency power output from
antenna
Maximum of 10 mW (10 dBm) EIRP
Maximum of 40 mW (16 dBm) EIRP for WN2 High Gain option
A.1.5 Environmental
Operating Temperature Range:
-40 to 158 °F (-40 to 70 °C)
Operating Humidity Range:
10-90% relative humidity
A.1.6 EMC performance
Complies with EN61326-1:2006.
A.1.7 Antenna options
Integrated Omni-directional Antenna
Optional remote mount Omni-directional Antenna
A.2 Physical specifications
A.2.1 Weight
10 lb. (4,54 kg)
A.2.2 Material of construction
Housing
Low-copper aluminum, NEMA
®
4X
Paint
Polyurethane
Cover gasket
Silicone Rubber
Antenna
Integrated Antenna: PBT/PC
Remote Antenna: Fiber Glass
1. The current consumption is for Gateway operation only. If using PSE,
calculations will need to be made to include the device being powered.
24
30
125
250
Current (mA)
12
10.5
Operating
Region
Voltage (VDC)