Reference Manual
00809-0200-4420, Rev HC
Appendix C: DeltaV Ready
July 2015
67
DeltaV Ready
Figure C-4. Gateway Context Menu (Right Click)
Now the Gateway and wireless devices are fully commissioned and available to use in other
DeltaV applications. When new devices are added to the wireless network, they will need to be
assigned to DeltaV channels through the reconcile process (right click on Gateway and select
configure IO).
Note
Logging in to the Gateway is not possible using the default TCP/IP network setting. If the
Gateway is decommissioned, use an IP address 10.5.255.254. If the Gateway is commissioned,
right click on the Gateway in DeltaV Explore and select Wireless Gateway Web Interface.