20
February 2020
Installation and Maintenance Instructions
MAN-02-04-99-0712-EN Rev. 1
Installation
Section 4: Installation
Table 4. Current Absorption - Three-Phase Voltage
Model
Selected
Step
Operating
Time
(s/90°)
Current Absorption (A)
208 V AC 240 V AC 380 V AC 400 V AC 480 V AC 500 V AC 575 V AC
063/E006
8 15 0.226 0.176 0.107
6 28 0.165 0.101 0.080
4 48 0.132 0.083 0.057
125/E013
8 15 0.344 0.227 0.171
6 28 0.295 0.180 0.143
4 48 0.245 0.155 0.125
250/E025
8 15 0.800 0.73 0.52 0.49 0.37 0.340
6 28 0.590 0.56 0.41 0.35 0.29 0.280
4 48 0.530 0.50 0.37 0.30 0.27 0.250
500/E051
8 15 1.073 0.97 0.65 0.58 0.46 0.430
6 28 0.720 0.64 0.47 0.39 0.32 0.310
4 48 0.590 0.55 0.41 0.32 0.29 0.280
1000/E091
8 24 1.073 0.97 0.65 0.58 0.46 0.430
6 45 0.720 0.64 0.47 0.39 0.32 0.310
4 80 0.590 0.55 0.41 0.32 0.29 0.280
2000/E171
8 53 1.073 0.97 0.65 0.58 0.46 0.430
6 100 0.720 0.64 0.47 0.39 0.32 0.310
4 180 0.590 0.55 0.41 0.32 0.29 0.280
NOTE
1. A = absorbed current (Amp) at nominal conditions (output torque 100%)
2. Max current (Amp) at stall conditions = 1.2 x A
3. Power factor for V AC supply = 0.60
4. Peak current: max 8xIn
5. Peak current duration: less than 0.1 s