38
February 2020
Installation and Maintenance Instructions
MAN-02-04-99-0712-EN Rev. 1
Actuator Configuration
Section 6: Actuator Configuration
6.2.13 Actuator Model Selection
The frames relevant to models 63/125 and 250/500 can be set to operate with a 63 Nm or
125 Nm motor and a 250 Nm or 500 Nm motor respectively. The difference is based on the
technical characteristics of the electric motor itself.
Actuator model 63
• Enter setup conguration: move switch SW3 to position ON (conguration function)
• Move switch SW4 to position 9
• Move switch SW6 to position 0
• Conrm by pushing ENTER pushbutton, SW5
• When pushing SW5, the red LED switches on for conrmation
• Exit setup conguration (move switch SW3 to position 1) or proceed to the
next parameter
Actuator model 125
• Enter setup conguration: move switch SW3 to position ON (conguration function)
• Move switch SW4 to position 9
• Move switch SW6 to position 1
• Conrm by pushing ENTER pushbutton SW5
• When pushing SW5, the red LED switches on for conrmation
• Exit setup conguration (move switch SW3 to position 1) or proceed to the
next parameter
Actuator model 250
• Enter setup conguration: move switch SW3 to position ON (conguration function)
• Move switch SW4 to position 9
• Move switch SW6 to position 0
• Conrm by pushing ENTER pushbutton SW5
• When pushing SW5, the red LED switches on for conrmation
• Exit setup conguration (move switch SW3 to position 1) or proceed to the
next parameter