Actuator Configuration
Section 6: Actuator Configuration
6.2.11 Conguration of the Torque Limiting Device in Opening
Opening torque limits are 50%, 75% and 100% of the nominal torque. The nominal torque
corresponding to 100% is set in-house and is stated on the nameplate.
Enter setup conguration: move switch SW3 to position ON (conguration function)
Move SW4 switch to position 7
Move switch SW6 to positions 2,5 or 9 for the requested torque value
(in percentage) in opening
Push ENTER pushbutton SW5 to conrm
When pushing SW5, the red LED switches on for conrmation
The setting of the torque limiting device in opening is now complete
Exit setup conguration (move switch SW3 to position 1) or proceed to the
next parameter
NOTICE
Consult the valve manufacturer torque specications for correct limit torque conguration.
WARNING
Installation, conguration, commissioning, maintenance, and repairs must be performed
by approved and qualied personnel only.
6.2.12 Reverse Mode Conguration
Enter setup conguration: move switch SW3 to position ON (conguration function)
Move switch SW4 to position 8
Move switch SW6 to position:
1 counter-clockwise (CCW) ON
0 counter-clockwise (CCW) OFF
Push ENTER pushbutton SW5 to conrm
When pushing SW5, the red LED switches on for conrmation
Reverse mode (CCW) set is now completed
Exit setup conguration (move switch SW3 to position 1) or proceed to the
next parameter