Installation and Maintenance Instructions
MAN-02-04-99-0712-EN Rev. 1
Actuator Configuration
Section 6: Actuator Configuration
6.2.14 Blinker / Local Selector Conguration
The default conguration for Blinker / Local Selector relay is off (always Open). In Blinker
conguration the relay changes its status every 500msec (Motor Running function) as the
actuator is moving. In Local Selector conguration (with Local Interface OM3 installed), the
relay is CLOSED when OM3 switch is on REMOTE and the relay is OPEN when OM3 switch is
on LOCAL.
To congure Blinker or Local Selector monitoring function (when OM3 is present):
• Enter setup conguration: move switch SW3 to position ON (conguration function)
• Move switch SW4 to position 4
• Move switch SW6 to position 1 (Blinker) or 2 (Local Selector)
• Conrm by pushing ENTER pushbutton SW5
• When pushing SW5, the red LED switches on for conrmation
• Exit setup conguration (move switchSW3 to position 1) or proceed to the
next parameter
6.2.15 Three-Wires (3-Wires) / Two-Wires (2-Wires)
Remote Control Conguration
The SCE300 default remote control conguration is a Three-Wires (3-Wires)
Remote Control
3-Wires configuration operation
• Command on terminal 35 to OPEN,
• Command on terminal 36 to CLOSE
2-Wires configuration operation
• Command present on terminal 35 to OPEN,
• Command absent on terminal 35 to CLOSE;
• Terminal 36 not used
To congure Remote Control parameter:
• Enter set up conguration: move switch SW3 to position ON (conguration function)
• Move switch SW4 to position 9
• Move switch SW6 to position 5 (3-WIRES) or 6 (2-WIRES)
• Conrm by pushing ENTER pushbutton SW5
• When pushing SW5, the red LED switches on for conrmation
• Exit set up conguration (move switch SW3 to position 1) or proceed with the
next parameter