1592016130 XV300K EN MASTER r1.1 16.06.2015
XV300K
13/26
Maximum production pressure, above this the output is at the voltage
MotorMaxLim.
Min. P2
Max. Full Scale
Def. 25 bar
Voltage/speed of the pressure point P1.
Min. MotorMinLim
Max. V2
Def. 20%
Voltage/speed of the pressure point P2.
Min. V1
Max. MotorMaxLim
Def. 90%
11.3 HEATING CYCLE PARAMETERS [HEA] - CHILLER
Caution: The heating cycle can be replaced by a second cooling cycle [CO2] by changing the setting of the
parameter Second Mode.
Pressure of the voltage/speed V2 point.
Min. P_MAX
Max. P2
Def. 7 bar
Pressure of the voltage/speed V1 point.
Min. P1
Max. Full Scale
Def. 11 bar
CHILLER
11.0
P2
[IH]
bar
CHILLER
7.0
P1
[IH]
bar
CHILLER
90
V2
[IC]
%
CHILLER
20
V1
[IC]
%
CHILLER
25.0
P_MAX
[IC]
bar