1592016130 XV300K EN MASTER r1.1 16.06.2015
XV300K
16/26
12.3 HEATING CYCLE PARAMETERS [HEA] DRY COOLER
Caution: The heating cycle can be replaced by a second cooling cycle [CO2] by changing the setting of the
parameter Second Mode.
Temperature of the voltage/V2 speed point.
Min. T_MAX
Max. T2
Def. 22,0 °C
Temperature of the voltage/V1 speed point.
Min. T1
Max. 95 °C
Def. 24,0 °C
Maximum production temperature, over this the output is at the voltage
MotorMaxLim.
Min. 0 °C
Max. T1
Def. 21,0 °C
Voltage/speed of the temperature point T2.
Min. MotorMinLim
Max. V2
Def. 20%
Voltage/speed of the temperature point T1.
Min. V1
Max. MotorMaxLim
Def. 90%
DRY COOLER
V2
90
%
[IH]
DRY COOLER
V1
20
%
[IH]
DRY COOLER
T_MAX
21.0
°C
[IH]
DRY COOLER
T2
24.0
°C
[IH]
DRY COOLER
T1
22.0
°C
[IH]