12.1 PARAMETERS READING AND EDITING
The parameters windows display the name of the parameter, the
[identifying code] of the corresponding menu, the value of the parameter
and the unit of measure.
to go to the parameter below;
to go to the parameter above
To change the value of the parameter press , the arrow and the value of
the parameter in brackets mean that the system is in the parameter editing
mode, edit the value by pressing the following key:
to increase the value
to decrease the value
to save.
to return to the parameter
12.2 COOLING CYCLE PARAMETERS [CO1] DRY COOLER
Temperature of the voltage/V1 speed point.
Min. 0 °C
Max. T2
Def. 22,0 °C
Temperature of the voltage/V2 speed point.
Min. T1
Max. T_MAX
Def. 28,0 °C
Maximum production temperature, above this the output is at the voltage
MotorMaxLim.
Min. T2
Max. 95 °C
Def. 29,0 °C
Voltage/speed of the temperature point T1.
Min. MotorMinLim
Max. V2
Def. 20%
Voltage/speed of the temperature point T2.
Min. V1
Max. MotorMaxLim
Def. 90%
DRY COOLER
V2
90
%
[IC]
DRY COOLER
V1
20
%
[IC]
DRY COOLER
T_MAX
29.0
°C
[IC]
DRY COOLER
T2
28.0
°C
[IC]
DRY COOLER
T1
22.0
°C
[IC]
DRY COOLER
T1
->(12.0)
°C
[IC]
DRY COOLER
T1
12.0
°C
[IC]
CHILLER
CHILLER