Enabling of the kick start. This parameter is set for loads that need a torque
start to move at low speeds.
ON (Def.): function enabled OFF: function disabled
Factory settings reset: reset to standard parameters (except for the
operating time of the adjuster).
Caution: once entered the reset control through the key , the old settings
will be lost and the controller will be reset accoriding to the pre-setting
MP420_50
15.2 MOTOR SETTINGS
Allows setting manually the cos-phi of the load to enhance its adjusting.
Min. 0.1
Max. 1
Def. 0.8
Allows enabling a function that automatically detects the value of the cos-
phi of the motor and save it in the parameter COS-PHI (available only on
demand).
Caution: the controller will be restart and the output voltage will be
increased gradually up to the 100% to return to the basic setting value. The
whole process will be automatic and last few seconds
Minimum adjustable voltage, used to limit the load minimum speed.
Min. 15 %
Max. Max.Lim.
Def. 15%
Maximum adjustable voltage, used to limit the load maximum speed.
Min. Min.Lim.
Max. 100%
Def. 100%
Time employed by the adjuster to go from 0% to 100% of the output signal
0-10V.
Min. 0 sec
Max. 60sec
Def. 5 sec
Defines the enabling of the jump window specified in the parameters
“Sup.Min.Lim.1” and “Sup.Max.Lim.1” of the adjuster. It is enabled to
prevent events of mechanical resonance.
Def. OFF
Caution: this is a prioritary function on any operating cycle
Lower voltage of the jump window.
Min. 0%
Max. Sup.Max.Lim.1
Def. 20%
(this parameter is visualized only if “Suppress.1” is ON)