(this parameter is displayed only if “IN.TYPE [IB]” is on pwm fv)
Minimum input frecuency used for the PWM fv input.
Min. 2 kHz
Max. MaxPwm
Def. 2kHz
(this parameter is displayed only if “IN.TYPE [IB]” is on pwm fv)
Maximum input frecuency used for the PWM fv input.
Min. PWMmin
Max. 20kHz
Def. 18kHz
Defines the full scale value provided by the probes.
Min. 0 bar
Max. 1000 bar
Def. 50 bar
Defines the measurement unit visualized in the state menu and in the
operating parameters. Bar (Def.) / Millibar / Pascal / kiloPascal
Caution: numbers won’t be converted
Adjusting value of the temperature probe connected to input 1.
Min. -5 °C
Max. +5 °C
Def. 0 °C
[WITH S1 CARD]
Adjusting value of the temperature probe connected to input 2.
Min. -5 °C
Max. +5 °C
Def. 0 °C
Defines the second operating cycle (it can be activated with I1 contact).
Direct: first cycle COOL , second cycle COOL;
Reverse(Def.): first cycle COOL, second cycle HEAT
[WITH S1 CARD]
Defines the pressure reference based on the following criteria:
Automatic in. (Def.): priority to the signal of the higher probe in the cooling
cycle, of the lower probe in the heating cycle;
Minimum in.: priority to the lower signal of the two probes;
Maximum in.: priority to the higher signal of the two probes;
In.2: probe 2 (disables input 1);
In.1: probe 1 (disables input 2);
Defines the operating logic of the start (I3) contact.
Closed (Def.): enables the adjuster (start) with the contact closed;
Open: enables the adjuster (start) with the contact open