1592016130 XV300K EN MASTER r1.1 16.06.2015
NOTE:
The data are related to operate at 400V~ 50Hz. For 230V voltage supply or XV3xxK models at 440-460V all
current are the same.
(*) Max current refers to an enviroment temperature of 50°C for a maximum time of 10 second every 5 minutes.
5 TECHNICAL CHARACTERISTICS
230/400V~ +10%/-15%, (440/460V~ on demand)
IP55 self extinguishing plastic box, pollution degree 3
Class II at the command imputs (insulation of 4kV between
commands block and the device supplied parts). Class I as
regards the accessible parts
Phase lost, inside overheating, sensor missing, external
emergency (motor klixon)
WARNING: the regulator restores automatically
Protection against power surges Class II
Type 1(Y). Residual current motor < 15mA
For XV308-12-20-28-40K Class X, for XV350-60K Class M.
NORMATIVE According to safety directive, reference standard EN60730-1. According to electromagnetic directive, reference
standard EN 61800-3. With refer to some typical applications, the XV300K8-12-20 regulators are suitable for
residential and commercial ambients, while the XV300K 28-40-50-60 regulators are suitable for industrial ambients.
XV300K regulators are designed to be installed inside a machine or a standard electrical cabinet and are therefore
considered a component. The installer must guarantee that the machine conforms to such regulations.
CAUTION This control does not contain current harmonics filter and for applications on public network
power supply the installer must make ref. to EN 61000-2-4 and EN 61000-3-12.