1592016130 XV300K EN MASTER r1.1 16.06.2015
Defines the transmission speed on channel RS-485
Possible modes: 9600bps, 19200bps (Def.), 38400bps
Defines the type of parity on the serial transmission.
Possibles modes: None (Def.), even, odd
Defines the parity bit in the serial transmission.
Possible modes: 1=one bit (Def.), 2=two bits
Adjuster’s maximum time to receive the setting value on Modbus
transmission. Over this time the adjuster locks the outputs and starts the
emergency state.
Min. 1
Max. 240s
Def. 30s
15.5 DIAGNOSIS
Days and hours of operation of the adjuster
Caution: in case of reset this value won’t be reset
Internal temperature of the adjuster represented in Centigrades
Quantity of stops due to the missing of a power supply phase or high
disturbances in the power supply line
Quantity of stops due to the internal overheating
Quantity of stops due to an external emergency received on the terminal I4
Quantity of stops due to a breakdown/fault of the possible power supply
probe 4…20 mA