IC200CXEVO
usermanual
18
Dynamictrendofthesetpointin
coolingmodewithpositive
compensationdifferential.
Dynamictrendofthesetpointin
coolingmodewithnegative
compensationdifferential.
Wintercompensation
Inheatingmode,itispossibletoincrease/decreasethevalueoftheworkingsetpoint(parameter
St04)byavalueproportionaltoparameterSd02.IfparameterSd02assumespositivevalues,there
willbeanincrease,andifitassumesnegativevalues,therewillbeadecrease.
Theproportionofincrease/decreaseaccordingtotheoutsideairtemperaturevalueiscontrolledbya
compensationstartsetpoint(parameterSd04),andbytherelevantdifferential(parameterSd06)that
canassumepositiveornegativevalues.
Thecompensatedvalueofthesetpointcannotexceedthelimitsoftheworkingsetpointinheat
pumpmode;itcanthereforeassumeavaluenolowerthanSt05andnohigherthanSt06.
WhenparameterSd02=0isset,thefunctionisdeactivated.
Dynamictrendofthesetpointin
heatingmodewithpositive
compensationdifferential.
Dynamictrendofthesetpointin
heatingmodewithnegative
compensationdifferential