9.4Digitalinputfordomestichotwaterdoublesetpoint(option)
Thecontrollerallowsthedomestichotwaterworkingsetpointtobechangedbasedonactivation/
deactivationofasuitablyconfigureddigitalinput(terminals6101).
Ifthedigitalinputisactive,theunitcanbeswitchedonorputinstandbybypressingbutton
or(whenswitchingoff,thebuttonpresseddependsonthemodethatwasactivewhenthe
digitalinputfordomestichotwaterproductiononlywasactivated).
Whenthevalueisactive:
•anoffsetofthevalueofparameterES32isappliedtotheDHWsetpoint
 (parameterES32canassumepositiveornegativevalues,itcanthereforeassumeavalueno
lowerthanFS05andnohigherthanFS06);
•theconnection/disconnectiondifferentialofthecompressorsassumesthevalueES33
Whenthedigitalinputfordomestichotwater
productiononlyisactivethelowerdisplayshowsthe
labelOSA(OnlySAnitary).
9.3Digitalinputfordomestichotwaterproductiononly
Ifthedigitalinputconfiguredas“Enablingofdomestichotwaterproductiononly(terminals4001)is
active,thecontrollerisenabledfordomestichotwaterproductiononly;thermoregulationforthe
productionofhotorchilledwaterisdisabled.
sanitaryo
nly
do
ublesetsanitary