9.4Digitalinputfordomestichotwaterdoublesetpoint(option)
Thecontrollerallowsthedomestichotwaterworkingsetpointtobechangedbasedonactivation/
deactivationofasuitablyconfigureddigitalinput(terminals6101).
Ifthedigitalinputisactive,theunitcanbeswitchedonorputinstandbybypressingbutton
or(whenswitchingoff,thebuttonpresseddependsonthemodethatwasactivewhenthe
digitalinputfordomestichotwaterproductiononlywasactivated).
Whenthevalueisactive:
•anoffsetofthevalueofparameterES32isappliedtotheDHWsetpoint
(parameterES32canassumepositiveornegativevalues,itcanthereforeassumeavalueno
lowerthanFS05andnohigherthanFS06);
•theconnection/disconnectiondifferentialofthecompressorsassumesthevalueES33
Whenthedigitalinputfordomestichotwater
productiononlyisactivethelowerdisplayshowsthe
label“OSA”(OnlySAnitary).
9.3Digitalinputfordomestichotwaterproductiononly
Ifthedigitalinputconfiguredas“Enablingofdomestichotwaterproductiononly”(terminals4001)is
active,thecontrollerisenabledfordomestichotwaterproductiononly;thermoregulationforthe
productionofhotorchilledwaterisdisabled.