TICHOTWATERPRODUCTION
9
9.1Unitswithasingleusersideexchanger
Forunitswithasingleusersideheatexchanger,thecontrollerallowsthesanitaryhotwater
productionfunctiontobeactivatedandmanagedwithwatersidevalve.
Thefollowingmustbeinstalledonthesystem:a3wayvalvethatdivertstheflowofwatertotheuser
orsanitaryhotwaterstorageandatemperatureprobethatmeasuresitsvalue.
Thefunctionalityallowstheunittocontrolthetemperatureinsideastoragetankfordomestichot
water,throughthedomestichotwaterprobe,andtomanagethe3wayvalveoutsidetheunit.The
priorityisalwaysfordomestichotwaterproduction.
Heatpumpoperation:thevalvediverts
thesupplywatertothesystem.The
operatingsetisSetH(SetCifinchiller
mode).
Domestichotwateroperation:thevalve
divertsthesupplywatertowardsthe
storagetank.Theoperatingsetisalways
SetS.
Theproductionofdomestichotwaterisindicatedon
thedisplaybythesymbol:
Thisconfigurationmustbeassociatedwithasuitablysizedboilerinwhichtostorehightemperature
water.Theboilermusthaveawellforinsertionofthedomestichotwaterprobe,placedatthetop,
throughwhichthecontrolleroftheunitmonitorstheneedtoproducedomestichotwater.