Alarm code
Description Compressor (n) Compressors not involved
C(n)dt
Compressor high discharge temperature
OFF /
C(n)HP
Compressor
(n)
high pressure switch
OFF /
C(n)Mn
Compressor
(n)
maintenance
/ /
C(n)oP
Compressor
(n)
oil pressure switch / Oil level switch
OFF /
C(n)Pd
Compressor
(n)
oil differential
OFF /
FUNCTIONMENU
8
Toaccessthefunctionsmenu,pressandreleasethebutton.Thelistoffunctionscanbe
scrolledcyclicallyusingtheorbuttons.Confirmaccesstothedesiredfunctionwith
thebutton.
Afterenteringthefunctionsmenu,youwillbeabletodothefollowing:
• Viewandresetthealarmspresent(ALrM)
• Viewanddeletethealarmlog(ALOG)
• UploadtheparameterintotheHotKey(UPL)
• Enable–disableoneorthetwocircuits(CrEn)
• Enable–disableoneofthecompressors(COEn)
• Readandresetthenumberofcompressorrunninghour(Hour)
• Readandresetthenumberofcompressorstartsup(COSn)
• Readthecompressordischargetemperature(COdt)
• Readthecondensingfanspeedpercentage(Cond)
• Readthepercentageoftheproportionaloutputs(Pout)
• Viewtimecountingtonextdefrostcycle,underheatpumpmode,(dF)
• Readtheprobetemperaturesenabledtocontroltheauxiliaryoutput(uS)
• ReadprobetemperatureoftheremotepanelsVICX620(trEM)
• Readtemperature,pressure,setpointoftheelectronicexpansionvalve1(Et1)
• Readtemperature,pressure,setpointoftheelectronicexpansionvalve2(Et2)
• Enable–disableevaporatororcondenserwaterpumps(PoEn)
TheALrMmenushowsallthealarmspresentinthe
unit.Ifthealarmisatautomaticreset,thealarm
messagewillalsoberemovedwhenthealarmis
terminated.
Ifthealarmisatmanualreset,thealarmcodeandthe
word"rst"or"no"willbedisplayeddependingon
whetherthealarmisresettableornot.
Pushorkeytoscrollthealarmlist.
Pushtoresetthealarm(onlywithlabel"rSt"displayed,nothinghappenswhen"no"labelis
displayed)
8.1Alarmlist(readandreset)