IC200CXEVO
usermanual
6
Condenserfan:ONifatleastonecondenserfanisactive
ONwhenthecompressorisactive
Blinking=whenacompressoractivationisdelayed(minimumOFFtime,delay
afterwaterpumpactivation,etc.)
ONwhenanauxiliaryoutputisactive
ONiftheunitisswitchedONincoolingorheating
2.3Displayvisualization
Allunitsareequippedwithadigitalinputwithremoteon/offfunction(refertothewiringdiagramto
identifytherelevantterminals).Theremoteoffcontacthaspriorityoverthekeyboardcommands,i.e.
itisnotpossibletostarttheunitfromthekeyboard(orfromremotesupervisionviaserialport)until
theremotepoweroncontactisenabled(contactclosedontheterminalboard).Theremoteoffunit
statusisindicatedonthedisplaybythelabelOFFwithaflashingLED.
Oncetheunithasbeenstartedalsofromthekeyboard,theupperlineofthedisplayshowsthe
regulationprobe(waterinlettemperatureatthemainheatexchanger),whileinthelowerlinethe
outletwatertemperatureisshown.
Afterenablingtheunitclosingtheremoteon/offcontactthedisplayshowsthelabelSTBY(standby)
untilthedesiredoperatingmodeisselectedusingtheappropriatebutton(seebelowfordetails).