IC200CXEVO
usermanual
44
Timebandsfordomestichotwater
Thesecondsetpointfordomestichotwaterproductioncanbeactivatedthroughtimebandinstead
ofactivationfromdigitalinput.
ParametersES19toES31mustbesuitablyconfigured(timebandstart/endanddayofactivation).
Duringactivation,theunitwillproducedomestichotwaterontheworkingsetpointFS03+ES32with
differentialES33.
Thereare3settabletimebands,andoneormoretimebandscanbeactivatedforeachindividualday
oftheweek.
ParametersES19ES24definethestartandendofthe3timebands.
ES19 Startoftimeband1fordomestichotwater 00:0024:00
ES20 Endoftimeband1fordomestichotwater 00:0024:00
ES21 Startoftimeband2fordomestichotwater 00:0024:00
ES22 Endoftimeband2fordomestichotwater 00:0024:00
ES23 Startoftimeband3fordomestichotwater 00:0024:00
ES24 Endoftimeband3fordomestichotwater 00:0024:00
ParametersES25ES31defineactivationofthetimebandsintheindividualdaysoftheweek.
ES25 TimebandsactivatedforMonday
ES26 TimebandsactivatedforTuesday
ES27 TimebandsactivatedforWednesday
ES28 TimebandsactivatedforThursday
ES29 TimebandsactivatedforFriday
ES30 TimebandsactivatedforSaturday
ES31 TimebandsactivatedforSunday
ThemeaningsofthevaluesofparametersES25ES31areasfollows.
0=Notimebandenabled
1=Timeband1enabled
2=Timeband2enabled
3=Timeband1+2enabled
4=Timeband3enabled
5=Timeband1+3enabled
6=Timeband2+3enabled
7=Timeband1+2+3enabled