2
CLARKSON SLURRY KNIFE GATE VALVES
KGA+
Operators
Retainer flanges
Sleeves
FIGURE 1
2 INITIAL INSPECTION
1.  Examine entire valve and report any 
damageor discrepancies immediately.
2.  Sleeves: visually examine the sleeves 
interior, looking for chunking, irregularities 
or other damage. It is not recommended you 
remove the retainer flanges (if equipped). 
3.  Retainer flanges: sizes NPS 8 (DN 200) and 
below may or may not have the optional 
retainer flanges, retainer flanges are 
standard on sizes NPS 10 (DN 250) and 
larger. Visually examine the retainer flanges 
surfaces, looking for tears, irregularities or 
other damage. Check tightness of retainer 
flange bolting.
4.  Operators: standard manual handwheels 
may be shipped loose for field installation, 
be sure to fully tighten. 
5.  Valves are normally shipped with gate in 
open position, the recommended position 
for installation. Valves supplied with spring 
to extend (fail close) cylinder actuators are 
shipped with the gate in the closed position. 
The KGA+ should be installed with the gate 
in the open position, exercise caution when 
applying air to open this valve and then 
ensure that it is locked in the open position 
when installing in the line.
6.  Accessories: if provided, including 
solenoids, limit switches, positioners, 
etc., are tested for functionality prior to 
shipment. Examine carefully for damage 
which may occur during shipment.
1 GENERAL INFORMATION
1.  The KGA+ is a packingless, slurry knife 
gate valve. All the sealing is accomplished 
by the elastomeric sleeves in the valve 
housing. The sleeves also form the wear 
section for the valve. The gate is removable 
for inspection or replacement while the 
valveisin service.
2.  The KGA+ is BIDIRECTIONAL 
(two-way shut-off) product and can be 
installed without concern over direction of 
flow. Since they will shut-off equally with 
in either direction, you will find no arrows 
or other indicators of a direction of flow or 
seatside.
3.  Clarkson slurry knife gate valves are 
suitable for on-off service only. They are 
notto be used in a throttling application.
4.  The style, size, pressure rating and material 
selection are the responsibility of the piping 
system designer.
Secondary seal: the KGA utilizes a multipart 
gate wiper assembly to wipe the gate and 
reduce potential for discharge from the top of 
the valve where the gate enters the housing 
assembly. The KGA+ features a secondary seal 
assembly capable of being lubricated without 
disassembly. Similar to what is currently 
offered on the KGD; this new seal design 
incorporates an external lubrication fitting to 
directly inject lubrication into the seal’s interior 
(patent pending).
Simplified housing assembly: housing spacers 
found on the KGA have been eliminated from 
the KGA+ allowing for an easier disassembly / 
assembly process.
With these changes, spare parts and 
interchangeability with the prior design have 
been impacted. These changes are detailed 
inSections ‘Spare parts’ (KGA+ and KGA).
5.  All valves should be operated within the 
design pressure and temperature ranges. 
Under no circumstances should the valves 
be operated at conditions outside these 
parameters. Do not exceed 100% of the 
maximum pressure rating of the valve at 
anytime during its operation. Pressure 
spikes beyond the valve’s pressure rating 
are solely the responsibility of the user.