3
3 80 37 50
4 100 37 50
6 150 69 93
8 200 69 93
10 250 113 153
12 300 113 153
14 350 169 229
16 400 169 229
18 450 238 322
20 500 238 322
24 600 345 467
26 650 345 467
30 750 345 467
36 900 610 827
42 1050 610 827
48 1200 610 877
54 1350 1000 1355
60 1500 1000 1355
3 80 25 34
4 100 25 34
6 150 40 54
8 200 40 54
10 250 65 88
12 300 65 88
14 350 100 135
16 400 100 135
18 450 140 190
20 500 140 190
24 600 200 271
26 650 200 271
30 750 200 271
36 900 320 434
42 1050 320 434
48 1200 320 434
54 1350 600 443
60 1500 600 813
CLARKSON SLURRY KNIFE GATE VALVES
KGA+
TABLE 1 - MAXIMUM TIGHTENING TORQUESTANDARD FLANGES
Valve size
ft·lb N·mNPS DN
TABLE 2 - MAXIMUM TIGHTENING TORQUE FRP FLANGES
Valve size
ft·lb N·mNPS DN
Installation notes
A)  All slurry knife gate valves are designed and 
manufactured to be installed in applications 
where no more than 1 g of force in excess 
of gravity is applied to the valve in any 
direction. This 1 g force can be an effect 
of traffic, wind, or earthquake, etc. Valves 
should not be used in applications that 
exceed 1 g.
B)  If valve stem or topworks protrude into 
walkways or work areas, valve should be 
flagged per company safety policy.
C)  All piping systems should contain 
independent support mechanisms and 
should not utilize the valve as a sole 
meansof support.
D)  Do not install valve over walkways, electrical 
or other critical equipment without the use 
of splash guards or similar considerations.
2.  The mating line flanges must be properly 
aligned prior to attempting installation. Slip 
on or weld flanges can be used. Never try to 
make up for misaligned pipe flanges by the 
line bolting. Pipe supports and/or expansion 
joints should be used to minimize pipe 
loads on valves. The pipeline companion 
flanges should be raised or flat face type to 
insure full sleeve support and a continuous 
unvarying I.D. If slip-on flanges are used, 
the pipe should be cut square and welded in 
position with the pipe end matched evenly 
with the flange face. Studded flanges are not 
compatible with these valves. Tables 1 and2 
state the maximum flange bolt tightening 
torques. Listed in Table 3 are the fasteners 
required for installation.
3.  Sizes NPS 8 (DN 200) and below may or 
may not have the optional retainer flanges. 
Retainer flanges are standard on sizes 
3 INSTALLATION INSTRUCTIONS
Please take note of the specific installation 
tagsprovided with each valve.
1.  The KGA+ is installed with the gate in the 
fully open position with the sleeves inserted 
into the housing halves.
CAUTION
Valves are normally shipped with gate in 
open position, the recommended position for 
installation. Valves supplied with spring to extend 
(fail close) cylinder actuators are shipped with 
the gate in the closed position. Gate should be 
actuated to the open position prior to installation, 
exercise extreme caution when applying air 
to open this valve and then ensure that it gate 
lockedin the open position for installation.
NPS 10 (DN 250) and larger. Ifnoretainer 
flanges are used, the flanged end of the 
sleeves form the gasket when installed 
into the pipeline. When equipped with 
retainer flanges, the elastomer coated 
retainer flange functions as the gasket 
forinstallation into the pipeline.
4.  Valve is suitable for use in either vertical or 
horizontal lines. The valve can be installed 
in any position in vertical or horizontal 
pipelines. However, valves installed in 
an orientation with the actuator below 
horizontal may require flushing to prevent 
the buildup of solids in the housing and may 
require additional actuator support.
5.  Standard mating flanges NPS 3 - 24 
(DN 80 - 600) match ASME B16.5/150, 
sizesNPS 26 (DN 650) and largerare per 
MSS-SP44 (see Table 1).