Maintenance
28
6.3 Precautions
Although the Liebert
®
GXT3
has been designed and manufactured to ensure personal safety,
improper use can result in electrical shock or fire. To ensure safety, observe the following precautions:
Turn Off and unplug the Liebert GXT3 before cleaning it.
Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.
Never block or insert any objects into the ventilation holes or other openings of the UPS.
Do not place the Liebert GXT3 power cord where it might be damaged.
6.4 Checking UPS Status
Emerson recommends checking the UPS operation status every six months.
Check whether the UPS is faulty: Is the Fault Indicator On? Is the UPS sounding an alarm?
Check whether the UPS is operating in Bypass Mode. Normally, the UPS operates in Normal
Mode. If it is operating in Bypass Mode, stop and contact your local Emerson representative, or
Emerson Channel Support.
Check whether the battery is discharging. When the mains input is normal, the battery should
not discharge. If the UPS is operating in Battery Mode, stop and contact your local Emerson rep-
resentative or Emerson Channel Support.
6.5 Checking UPS Functions
Emerson recommends checking the UPS functions once every six months.
Back up the load data before conducting the UPS functions check. Procedures are as follows:
1. Press the Standby/Manual Bypass button to check whether the buzzer and indicators are normal.
2. Press the On/Alarm Silence/Manual Battery Test button to check again whether the indicators
are On and the UPS is operating normally.
3. Press the On/Alarm Silence/Manual Battery Test button for three seconds after Inverter Mode.
The UPS should initiate a battery self-test. Check to determine whether the battery is operating
normally. If not, stop and contact your local Emerson representative or Emerson Channel Support
NOTE
UPS function check procedures may interrupt power supply to the connected load.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Liebert GXT3 and is the answer not in the manual?

Emerson Liebert GXT3 Specifications

General IconGeneral
ModelLiebert GXT3
Relative Humidity0-95% non-condensing
TypeOnline Double Conversion
Input Frequency50/60 Hz
Output Frequency50/60Hz ±0.1%
Power Factor0.9
Form FactorTower or Rackmount
Battery TypeSealed Lead-Acid (SLA)
Communication InterfaceRS-232, USB
Operating Temperature0° to 40°C (32° to 104°F)
Storage Temperature-15°C to 40°C (5°F to 104°F)
DimensionsVaries depending on the specific model
WeightVaries depending on the specific model
CertificationsUL, cUL, CE, RoHS

Related product manuals