Specifications
34
Table 12 Specifications of the Liebert
®
GXT3
-1500RT230, GXT3-2000RT230 and GXT3-3000RT230
Parameters
Product model
GXT3-1500RT230 GXT3-2000RT230 GXT3-3000RT230
Model Rating 1500VA/1350W 2000VA/1800W 3000VA/2700W
Dimensions, D x W x H, mm (in)
Unit
497 × 430 × 85
(19.6 x 16.9 x 3.3)
602 × 430 × 85
(23.7 x 16.9 x 3.3)
Shipping
617 x 570 x 262
(24.3 x 22.4 x 10.3)
717 x 570 x 262
(28.2 x 22.4 x 10.3)
Weight, kg (lb)
Unit 23.2 (51.1) 25.5 (56.1) 32.4 (71.4)
Shipping 26 (57.3) 28 (61.7) 35 (77.2)
Input AC
Voltage Range (typical) 230VAC nominal; variable based on output load
90% ~ 100% loading 177VAC/280VAC 196VAC/280VAC
70% ~ 90% loading 168VAC/280VAC 184VAC/280VAC
30% ~ 70% loading 150VAC/280VAC 161VAC/280VAC
0 ~ 30% loading 115VAC/280VAC 115VAC/280VAC
Frequency 40Hz ~ 70Hz; Auto Sensing
Input Power Receptacle C14 C20
Output AC
AC-AC Efficiency >
88% AC-AC, minimum
Output Receptacles C13 x 6 C13 x 6; C19 x 1
Voltage 220/230/240VAC (user configurable); ±3%
Frequency 50Hz or 60Hz
Waveform Sine wave
Mains (AC) Mode Overload
200% for 2 seconds; 150% for 50 seconds
200% for 2 seconds;
150% for 55 seconds
Internal Battery Charger
Charger Current 1.88
2.71 2.5
Battery
Type Valve-regulated, nonspillable, lead acid
Qty × V× Rating 4 × 12V × 7.2Ah 4 × 12V × 9.0Ah 6 × 12V × 9.0Ah
Battery Mfr/Part# Panasonic/UP-RW1236
CSB/ GP 1272
Panasonic/UP-RW1245
CSB/ HR 1234W F2
Backup Time See Table 15 - Battery run time
Recharge Time
3 hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown
(Internal Batteries Only)
Environmental Requirements
Operating Temp 0ºC to 40ºC (32ºF to 104ºF); Table 14 - Operating temperature parameters
Storage Temp -15ºC to +50ºC (5ºF to 122ºF)
Relative Humidity 0%RH to 95%RH, non-condensing
Operating Elevation
Up to 3000m (10,000 ft.) at 25ºC (77ºF) without derating
Storage Elevation 15000m (50,000 ft.) maximum
Audible Noise
< 45 dBA max. at 1 meter (3.2ft.) front and side
< 46 dBA, at 1 meter (3.2ft.) rear
< 48 dBA max. at 1 meter (3.2ft.) front and side
< 48 dBA, at 1 meter (3.2ft.) rear
Agency
Safety IEC/EN/AS 62040-1:2008, GS mark
RFI/EMI IEC/EN/AS 62040-2 2nd Ed (Category C2) = CISPR22 Class A
Surge Immunity IEC/EN 62040-2 2nd Ed (IEC/EN 61000-4-5)
Transportation ISTA Procedure 1A