EasyManua.ls Logo

Emerson Liebert GXT3 - Table 15 Battery Run Times

Emerson Liebert GXT3
46 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specifications
36
Table 15 Battery run times
Number of
Batteries/Cabinets
Load Percent
of Capacity
Run Time, Minutes
700VA 1000VA 1500VA 2000VA 3000VA
Internal Battery
10% 105 91 75 73 77
20% 62 38 35 33 37
30% 37 31 22 21 21
40% 32 23 16 15 15
50% 27 17 11 11 11
60% 22 14 10 8 8
70% 18 11 6 6 6
80%159555
90%138444
100%116433
Internal Battery
+ 1 External Battery
Cabinet
10% 307 214 194 166 182
20% 183 153 131 121 123
30% 150 124 96 79 79
40% 131 100 72 41 53
50% 109 79 41 38 46
60% 98 66 38 34 38
70% 81 41 35 30 31
80% 72 38 32 25 26
90% 63 36 27 21 21
100% 41 34 23 17 18
Internal Battery
+ 2 External Battery
Cabinets
10% 374 337 310 306 311
20% 314 216 185 159 160
30% 212 166 148 133 134
40% 186 152 126 105 105
50% 160 136 103 81 81
60% 149 121 83 67 68
70% 139 104 72 40 52
80% 128 93 62 38 47
90% 112 79 40 36 43
100% 105 71 38 33 38
Internal Battery
+ 3 External Battery
Cabinets
10% 480 480 339 331 335
20% 341 322 225 202 205
30% 319 219 184 157 157
40% 225 191 154 138 139
50% 206 161 139 120 120
60% 187 151 123 99 100
70% 163 140 105 80 81
80% 155 128 93 70 71
90% 148 112 79 60 62
100% 141 105 71 40 51