Reference Manual
00809-0100-4716, Rev JA
May 2008
3-33
Rosemount 3095 MultiVariable
HART
Set up Tri-loop
Configuration
1. Start AMS.
2. Right-click the on-line 3095 and select Configuration Properties.
3. Select the HART tab.
4. Select Burst Mode Off.
5. Select Burst option to processvars/crnt. This is HART command 3.
Select Apply and OK.
6. Exit Configuration Properties.
7. Right-click on the Tri-Loop icon and select Configuration
Properties.
8. In Basic Setup, enter the desired tag name. View device information
and channel enable.
9. Select Channel 1 tab. Select desired Process variable. Input units,
upper range value, low Range and Enabled to Yes. Select Apply.
10. Select Channel 2 tab. Select desired Process variable. Input units,
upper range value, low Range and Enabled to Yes. Select Apply.
11. Select Channel 3 tab. Select desired Process variable. Input units,
upper range value, low Range and Enabled to Yes. Select Apply.
12. If necessary, perform an analog output trim on each of the 4-20 loops
on the 333 HART Tri-Loop.
13. After all configuration steps have been completed for the 333
Tri-Loop and the 3095 transmitter, AND the flow configuration file has
been sent to the 3095 transmitter, return to the Configuration
Properties functions of the 3095M and go to the HART tab to set the
Burst Mode to On.
Flow Configuration Flow configuration for the 3095 is achieved by launching the 3095 Snap-On
application from the Device Configuration screen. The following steps
highlight how to access the flow configuration program for the 3095:
1. Right-click on the transmitter icon.
2. Highlight “SNAP-ON” from the pop-up menu.
3. Click “MultiVariable Engineering Assistant” from the submenu.