Reference Manual
00809-0100-4716, Rev JA
May 2008
3-47
Rosemount 3095 MultiVariable
HART
Off-line Configuration In off-line mode, the 3095 Engineering Assistant does not communicate
directly with the transmitter. Instead, the configuration file is saved to the
computer and loaded onto the transmitter at a later time when in on-line
mode. To launch the 3095 MultiVariable Engineering Assistant in off-line
mode:
1. When at the default Device Connection view, double click on the
“Plant Database” icon.
2. Expand the “Area” folder by clicking on the “+” box.
3. Expand the “Unit” folder.
4. Expand the “Equipment Module” folder.
5. Right-click on the “Control Module” folder.
6. Select “Add Future Device” from the pop-up menu.
7. Select “3095 template” from the list of devices and click “OK.”
8. Right-click on the transmitter icon.
9. Launch the MultiVariable Engineering Assistant application (located
under the SNAP-ON menu for AMS Snap-on users).
From here you can open up the flow configuration wizard and save a flow
configuration file (.mv file). Follow the same procedure for creating a flow
configuration as found on page 3-33 or page 3-36.