Reference Manual
00809-0100-4716, Rev JA
May 2008
4-21
Rosemount 3095 MultiVariable
FIELDBUS
BLK_TAG_#
(1)
Enter the Block Tag of the function block that contains the parameter to be
displayed. The default function block tags from the factory are:
BLK_TYPE_#
(1)
Enter the Block Type of the function block that contains the parameter to be
displayed. This parameter is generally selected via a drop-down menu with a
list of possible function block types. (e.g. Transducer, PID, AI, etc.)
PARAM_INDEX_#
(1)
The PARAM_INDEX_# parameter is generally selected via a drop-down
menu with a list of possible parameter names based upon what is available in
the function block type selected. Choose the parameter to be displayed.
CUSTOM_TAG_#
(1)
The CUSTOM_TAG_# is an optional user-specified tag identifier that can be
configured to be displayed with the parameter in place of the block tag. Enter
a tag of up to five characters.
UNITS_TYPE_#
(1)
The UNITS_TYPE_# parameter is generally selected via a drop-down menu
with three options: AUTO, CUSTOM, or NONE. Select AUTO only when the
parameter to be displayed is pressure, temperature, or percent. For other
parameters, select CUSTOM and be sure to configure the
CUSTOM_UNITS_# parameter. Select NONE if the parameter is to be
displayed without associated units.
CUSTOM_UNITS_#
(1)
Specify custom units to be displayed with the parameter. Enter up to six
characters. To display Custom Units the UNITS_TYPE_# must be set to
CUSTOM.
(1) _# represents the specified parameter number.
TRANSDUCER CHAR 2400
AI 1400 AO 1900
PID 2000 CSEL 2500
INTEG 2100 OSPL 2600
ISEL 2200 MASS FLOW 1200
ARITH 2300