Prm.No.
DefinitionofParameter
Unit
Lower/UpperLimit
Default
P00
Mainsvoltageconnectionlevel
VAC
60-600
320
P01
Mainsvoltagedisconnectionlevel
VAC
60-600
300
P02
Mainsvoltageupperlimit
VAC
60-600 440
P03
Alternatorvoltagelowerlimit
VAC
60-600
320
P04
Alternatorvoltageupperlimit
VAC
60-600 440
P51
Hz.
30.0-75.0 43.0
P06
Number
1-10
3
P09
Mainstransitiondelay
Minute
0-30 3
P10
Single/ Threephaseselection
Select
1PH/3PH
3PH
P11
Batteryvoltagelowerlimit
VDC
7.2-24.0 8.0
P13
Stop/Fuelsolenoidselection
StoP /FuEL
FuEL
P14
Stopmagnetenergisingtime
0-99 20
P16
Startingattemptduration
5-99
5
P18
Speedlimitforcrankdisconnection
20.0-45.0 40.0
P19
Controlondelay
0-99 10
P20
Alternatorvoltagefaultcontroldelay
0.0-10.0 5.0
P21
Speedfaultcontroldelay
Second
5.0
P24
Hornoutputselection;
0= Alarmoutput
1=Chokeoutput
2=Simulatefuelsolenoidoutput
0-2 0
P25
Choketime
0.8
P15.0
P15.1
P15.2
P15.3
P07
P08
P12
P15
P17
P22
P23
Speedlowerlimit
Numberofstartingattempts
Enginecoolingtime
Hornduration
Mains-GeneratororGenerator-Mains
changeoverdelay
Configurablefailureinput-2(Pin10)
ThesameasP22
Configurablefailureinput-1(Pin9)
Alternatorvoltagelimitforcrank
disconnection
Enginestartedsignal
Chargegenerator
Speed
Alternatorvoltage
Oilpressure
0
1
2
3
4
5
6
LEDflashesandhornsounds.
Itisunlatched.
LEDflashesandhornsounds
andthenstaysonuntilreset.
As"1"plusenginestops.
As"0"butonlywhileenginerunning.
As"1"butonlywhileenginerunning.
As"4"plusenginestopsifrunning.
As"4"plusgeneratorcontactor
de-energised,ifenginerunning.
Minute
Second
Second
Select
Second
Select
Second
VAC
Hz.
Second
Second
Number
Number
Number
Second
0-999
0-99
0=disablescoolingprocess
0.1-25.0
no/ YES
40-360
0-8
0- 8
0=continuous
no/ YES
no/ YES
no/ YES
0.0-10.0
0.0-30.0
3
60
1.0
No
YES
No
300
0
0
P26
Generatorstartdelay
0-9999 0
P27
P28
Oilsensorselection
EngineRunning Time
0
0
Second
Number
Hour
0-1
0-9999
PoPS
Operatorpassword(P00toP09,andPoPS)
0-9999 0
PtPS
Technicianpassword(P00toPtPS)
0
Number
Number
0-9999
P52
Hz.
30.0-75.0 53.0
Speedupperlimit
P191
Oilfailurecontroldelay
0.0-25.0 0.0
Second
7
8
Remoteinhibit
Remotestart
4.4ParameterList
25
No