32
1.Checkthatthemainsisconnectedtotheunitandispresent.
2.Checkthemainsvoltagereadingsonthedisplay.
3. AttheEAOM-19,pressthe AUTO(18)button. TheLED(7)onthebuttonshouldlight.
4.Switchoffthemainssupplytotheunit.Checkthatthegeneratorstartsand,afteradelay,
theloadistransferredtothegenerator.
5.Restorethemainssupplytotheunit.Checkthat,afteradelay,theloadistransferredback
tothemainsandthegenerator,afterafurtherdelay,shutsdown.
1.Checkthatthemainsisconnectedtotheunit.
2.Pressthe TEST (11)button. AtthismomenttheLED(1)willlighton.
3.Checkthatthegeneratorstartsandthattheloadisstillconnectedtothemains.
4.Switchoffthemainssupply.Checkthatthecontactorschangeovertoconnecttheloadto
thegenerator.Checkalsothatthe (7)LEDislit. Theunitchangesoperatingmodeto
AUTOModeautomatically.
5.Restorethemainssupply.Checkthatthecontactorsreconnecttheloadtothemains
supply.
6.Checkthatthegeneratorshutsdownwithcool-downperiod.
Auto
5.2 AutoMode
5.3TestMode