EasyManua.ls Logo

Emotron M20 - Page 46

Emotron M20
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CG Drives & Automation 01-5958-01r0
Terminal tighten-
ing torque
0.56-0.79 Nm (5-7 lb-in)
Accuracy
±2%, ±1 unit cos phi>0.5; excl. current transformer; +20°C
(+68°F)
Repeatability ±1 unit 24h; +20°C (+68°F)
Temperature toler-
ance
max 0.1%/°C
Operating temper-
ature
-20 to +50°C (-4°F to +122°F)
Storage tempera-
ture
-30 to +80°C (-22°F to +176°F)
Protection class IP20
RoHS directive 2002/95/EC
Approved to CE (up to 690VAC), UL and cUL (up to 600 VAC)
Article
number
Designation
01-2520-25 Emotron M20 1x100-240/3x100-240 VAC
01-2520-45 Emotron M20 3x380-500 VAC
01-2520-55 Emotron M20 3x525-690 VAC