Commissioning Cerabar M HART
32 Endress+Hauser
6.3.5 Lower-range and upper-range value: setting without reference
pressure
The desired pressure for the lower-range value (zero point) and the upper-range value is set using
the handheld terminal without specifying a reference pressure.
6.3.6 Lower-range and upper-range value: setting with reference
pressure
A reference pressure is available which corresponds exactly to the desired lower-range value (zero
point) and the desired upper-range value.
Main group: Basic calibration
# Matrix (VH position) Path through the menus Entry
1 Enter known pressure for the lower-range value
P01-PMx4xxxx-19-xx-xx-xx-033
Fig. 33: No reference pressure
V0H1 Set 4 mA e.g. 0 psi
Enter
2 Enter known pressure for the upper-range value
V0H2 Set 20 mA e.g. 14.5 psi
Enter
Main group: Basic calibration
# Matrix (VH position) Path through the menus Entry
1 Accept pressure present for the lower-range value
P01-PMx4xxxx-19-xx-xx-xx-034
Fig. 34: Reference pressure
V0H3 Confirm 4 mA
automatically
e.g. 0 psi
Enter
2 Accept pressure present for the upper-range value
V0H4 Confirm 20 mA
automatically
e.g. 14.5 psi
Enter