Commissioning iTEMP TMT142B
36 Endress+Hauser
Reference junction
RJ preset value
In the third section, the settings are made for the analog output and the output's alarm
response. The following parameters can be configured:
Navigation Guidance → Commissioning → Current output
A0053295
4 mA value
20 mA value
Failure mode
Failure current
In the final section, a password can be defined for the "Maintenance" user role. This is
strongly recommended to protect the device against unauthorized access. The following
steps describe how to configure a password for the "Maintenance" role for the first time.
Navigation Guidance → Commissioning → User management
A0053296
Access status
New password
Confirm new password
1. The Maintenance role appears in the "Access status" picklist. The Maintenance user
role must first be selected when operating the device with the SmartBlue App.
Afterwards, the New password and Confirm new password input boxes appear.
2. Enter a user-defined password that meets the password rules indicated in the online
help.
3. Enter the password again in the Confirm new password input box.
Once the password has been entered successfully, parameter changes, particularly those
that are needed for commissioning, process adaptation/optimization and troubleshooting,
can only be implemented in the Maintenance user role and if the password is entered
successfully.