iTEMP TMT71/72 Technical data
HART
®
specification 7
Device address in multi-drop mode Software setting addresses0 to 63
Device description files (DTM, DD) Information and files under:
www.endress.com
www.fieldcommgroup.org
HART load min. 250
HART device variables Measured value for primary process value (PV)
Sensor (measured value)
Measured values for SV, TV, QV (second, third and fourth device
variable)
SV: Device temperature
TV: Sensor (measured value)
QV: Sensor (measured value)
Supported functions Squawk
Condensed status
Wireless HART data
Minimum starting voltage 10 V
DC
Start-up current 3.58 mA
Starting time 7 s
Minimum operating voltage 10 V
AC
Multidrop current 4.0 mA
Time for connection setup 9 s
Write protection for device
parameters
Hardware: Write protection for head transmitter on optional display using DIP switch
Software: User role concept (password definition)
Switch-on delay 7 s until the first valid measured value signal is present at the current output and until
start of HART® communication. While switch-on delay = I
a
3.8 mA
13.3 Power supply
Supply voltage Values for non-hazardous areas, protected against polarity reversal:
Head transmitter: 10 V Vcc 36 V
Values for hazardous areas, see Ex documentation .
Current consumption • 3.6 to 23 mA
Minimum current consumption 3.5 mA
Current limit 23 mA
Terminals
Terminal version Cable version Cable cross-section
Screw terminals Rigid or flexible 2.5 mm² (14 AWG)
Endress+Hauser V. 1, Rev. 2, 4-10-2018 47