Technical data iTEMP TMT71/72
13.4 Performance characteristics
Response time The measured value update depends on the type of sensor and connection method and
moves within the following ranges:
Resistance thermometer (RTD) 1 s
Thermocouples (TC) 1 s
Reference temperature 0.9 s
Reference operating
conditions
When recording step responses, it must be taken into account that the times the
internal reference measuring point are added to the specified times where applicable.
Calibration temperature: +25 °C ±3 K (77 °F ±5.4 °F)
Supply voltage: 24 V DC
4-wire circuit for resistance adjustment
Maximum measured error In accordance with DIN EN 60770 and the reference conditions specified above. The
measured error data correspond to ±2 σ (Gaussian distribution). The data include non-
linearities and repeatability.
Typical
Standard Designation Measuring range Typical measured error (±)
Resistance thermometer (RTD) as per standard Digital value
1)
Value at current
output
IEC 60751:2008 Pt100 (1)
IEC 60751:2008 Pt1000 (4) 0 to +200 °C (32 to +392 °F)
0.07 °C (0.13 °F) 0.10 °C (0.18 °F)
0.05 °C (0.09 °F) 0.08 °C (0.14 °F)
GOST 6651-94 Pt100 (9) 0.06 °C (0.11 °F) 0.09 °C (0.16 °F)
Thermocouples (TC) as per standard Digital value
Value at current
output
IEC 60584, Part 1 Type K (NiCr-Ni) (36)
IEC 60584, Part 1 Type S (PtRh10-Pt) (39) 0 to +800 °C (32 to +1 472 °F)
0.60 °C (1.08 °F) 0.64 °C (1.15 °F)
1.83 °C (3.29 °F) 1.84 °C (3.31 °F)
GOST R8.8585-2001 Type L (NiCr-CuNi) (43) 2.45 °C (4.41 °F) 2.46 °C (4.43 °F)
1)
Measured value transmitted via HART
®
.
Measured error for resistance thermometers (RTD) and resistance transmitters
Standard Designation Measuring range Measured error (±)
Pt100 (1)
–200 to +850 °C
(–328 to +1 562 °F)
Maximum
3)
0.1 °C (0.19 °F)
Digital
1)
D/A
2)
In relation to measured
value
4)
ME = ± (0.05 °C (0.09 °F) +
0.006% * (MV - LRV))
IEC 60751:2008
Pt200 (2) 0.20 °C (0.36 °F)
Pt500 (3) –200 to +510 °C (–328 to +950 °F) 0.1 °C (0.19 °F)
Pt1000 (4) –200 to +250 °C (–328 to +482 °F) 0.06 °C (0.11 °F)
0.011% * (MV - LRV))
ME = ± (0.035 °C (0.063 °F)
+ 0.008% * (MV - LRV))
ME = ± (0.02 °C (0.04 °F) +
0.007% * (MV - LRV))
0.03 % (
4.8 µA)