iTEMP TMT71/72 Operating menu and parameter description
Time stamp n
Navigation Diagnostics → Event logbook → Time stamp n
Description Displays the time stamp of the current diagnostic message in relation to the operating
User interface Hours (h)
14.1.4 "Simulation" submenu
Diagnostic simulation
Navigation Diagnostics → Simulation → Diagnostic simulation
Description Switches diagnostic simulation on and off.
Selection Enter one of the diagnostic events using the dropdown menu → 39. The assigned
status signals and diagnostic behaviors are used in the simulation mode. Select 'Off' to quit
Example: x043 Short circuit
Factory setting Off
Current output simulation
Navigation Diagnostics → Simulation → Current output simulation
Description Use this function to switch simulation of the current output on and off. The status signal
indicates a category "C" diagnostic message ("function check") while the simulation is
Factory setting Off
Value current output
Navigation Diagnostics → Simulation → Value current output