iTEMP TMT71/72 Operating menu and parameter description
HART address
Navigation Application HART configuration HART address
Description Use this function to define the HART address of the device.
User entry 0 to 63
Factory setting 0
Additional information The measured value can only be transmitted via the current value is the address is set to
"0". The current is fixed at 4.0 mA for all other addresses (Multidrop mode).
1)
1) Can only be entered with FDT/DTM-based operating tools, e. g. FieldCare, DeviceCare from Endress+Hauser, but not via SmartBlue App.
No. of preambles
Navigation Application HART configuration No. of preambles
Description Use this function to define the number of preambles in the HART telegram.
User entry 5 to 20
Factory setting 5
14.3 Menu: System
14.3.1 Submenu: Device management
HART short tag
Navigation System Device management HART short tag
Description Use this function to define a short tag for the measuring point.
User entry Up to 8 alphanumeric characters (letters, numbers and special characters).
Factory setting 8 x '?'
Device tag
Navigation System Device management Device tag
Endress+Hauser V. 1, Rev. 2, 4-10-2018 81