iTEMP TMT71/72 Operating menu and parameter description
Additional information Value
A0014564
Value + bar graph
A0014563
Value 1 display (Value 2 or 3 display)
Navigation System Display Format display Value 1 display (Value 2 or 3 display)
Description Use this function to select one of the measured values to be shown on the local display.
The Format display parameter is used to specify how the measured values are
displayed.
Selection Process value
Device temperature
Output current
Percent of range
Off
Factory setting Process value
Decimal places 1 (decimal places 2 or 3)
Navigation System Display Format display Decimal places 1 (Decimal places 2 or 3)
Prerequisite A measured value is defined in the parameter Value 1 display (Value 2 or 3 display).
Description Use this function to select the number of decimal places for the display value. This setting
does not affect the accuracy of the device for measuring or calculating the value.
If Automatic is selected, the maximum possible number of decimal places is always
shown on the display.
Endress+Hauser V. 1, Rev. 2, 4-10-2018 95