11 Operation using PROFIBUS
®
PA TMT84
56 Endress + Hauser
11.2.2 Group Setup
Information on the device mode, such as the target mode, and parameters for the basic configuration
of the measuring inputs, such as the sensor type. All the settings that are needed to operate the
device can be made in the Standard setup mode. The individual parameters are summarized in the
Setup menu:
Selecting the operating mode
The operating mode is set by means of the "Physical Block - target mode" parameter group
(Page 57).
The Physical Block supports the following operating modes:
AUTO (automatic mode)
•Out of Service (OOS)
!
Note!
OOS can only be configured if the Condensed Status and Diagnostics (as per Profile 3.01 Am2) are
activated. Otherwise, only AUTO is supported.
Procedure for configuring a measuring input:
Standard setup Basic settings for the measuring inputs that are needed to commission the device.
Advanced setup Configuration of special diagnostics functions such as drift or corrosion detection.
Advanced setup 
Page 60
Sensor 1
Setup Page 56 Sensor 2
Security settings
1. Start
2. Select sensor type (linearization type) e.g. Pt100
3. Select unit (°C)
4. Select type of connection e.g. 3-wire
5. Configure the type of measurement e.g. PV=SV1
6. Enter the offset (optional)
7. Select the reference measuring point and enter the value in the event of external reference measurement
(only for TC measurement)
8. If a second measuring channel is used, repeat steps 2 to 5
9. End