11 Operation using PROFIBUS
®
PA TMT84
64 Endress + Hauser
Submenu Diagnostics - Measured values
This menu is only visible in the online mode.
n: Number of the Transducer Block (1-2) or the sensor input (1 or 2)
Device TAG read/
write
Entry of a user-specific text of max. 32 characters for
unique identification and assignment of the block.
Factory settings:
"– – – – – – – –" no text
ENP version read Displays the ENP (electronic name plate) version.
Profile read 0x4002 - PROFIBUS PA, Compact Class B
Profile Revision read Displays the profile version implemented in the device.
Manufacturer read Displays the manufacturer ID number.
Display:
0x11(hex);17 (decimal): Endress+Hauser
Product designation read Displays the manufacturer-specific device designation.
Display:
iTEMP TMT84
PROFIBUS Ident
Number
read Displays the Profibus User Organization identification
number of the device.
– 0x1523
TMT184
–0x1551
TMT84
– 0x9700
Profile Ident Number 1x AI Block
– 0x9701
Profile Ident Number 2x AI Block
– 0x9702
Profile Ident Number 3x AI Block
– 0x9703
Profile Ident Number 4x AI Block
Factory settings:
0x1551
1. These parameters may be changed if the parameter "Service locking" in the expert
menu is set correspondingly.
Measured values
Menu item Parameter
"Diagnostics"
Submenu
"Measured values"
Name
Parame-
ter access
Description
PV value n
read
Displays the primary output value of the Transducer
Block.
! Note!
The PV value n can be made available to an AI Block for
further processing.
Process temperature
n
read Displays the measured value of sensor n.
Reference Junction
Temperature
read Internal reference temperature measurement.
System information
Menu item Parameter
"Diagnostics"
Submenu "System
information"
Name
Parame-
ter access
Description