11 Operation using PROFIBUS
®
PA TMT84
66 Endress + Hauser
Submenu Diagnostics - Device test/reset
This menu is only visible in the online mode.
By means of a reset, the device can be set to a defined state depending on the reset code.
Device test/reset
Menu item Parameter
"Diagnostics"
Submenu
"Device test/reset"
Name
Parame-
ter access
Description
Reset read/
write
Resets or restarts the device.
User input:
0
No function/no action
1
Standard configuration/reset all bus-specific param-
eters to factory settings with the exception of the config-
ured station address.
The device displays the next cold start for 10 seconds in
the corresponding bit of the DIAGNOSTICS parameter
group.
2506
Warm start/execution of a warm start.
The device displays the next warm start for 10 seconds in
the corresponding bit of the DIAGNOSTICS parameter
group.
2712
Resets address to '126'/resets the station
address to the usual PROFIBUS default address 126.
32769
Configuration ordered/resets to delivery sta-
tus.
Factory settings:
0
" Caution!
If you select 1, the units are reset according to the factory
setting not delivery status. After resetting, check the units
and configure the unit you require. Then run the "Set
Unit To Bus" (Page 75) parameter.