TMT84 11 Operation using PROFIBUS
®
PA
Endress + Hauser 67
11.3 Setup Expert
The parameter groups for the Expert setup contain all the parameters of the Standard setup and
other parameters that are solely reserved for experts.
11.3.1 Group System
All the parameters that describe the measuring point in greater detail can be viewed and configured
in the "System" group.
System Page 67
Settings and description of the measur-
ing point
Display Page 54
Sensory mechanism Page 69
Settings of the two measuring inputs
Sensor 1 Special linearization 1
Sensor 2 Special linearization 2
Communication
Page 75
Settings of the Profibus address and
setup of the 4 Analog Input Blocks
Analog Input 1
Expert Page 67 Analog Input 2
Analog Input 3
Analog Input 4
Diagnostics Page 85
Displays device information and status
for service and maintenance purposes.
System information Page 63
Measured value Min./max. values Page 65
Device test/reset Page 66
System
Menu item Parameter
"Diagnostics" Name
Parame-
ter access
Description
Target Mode read/
write
For selecting the required operating mode.
Only automatic operation can be selected in the Physical
Block. The Physical Block can also be set to OOS if diag-
nostics is enabled as per Profile 3.02 (Physical Block
parameter "COND_STATUS_DIAG" = 1).
Options:
• 0x08 - AUTO
• 0x80 - Out of Service (OOS)
Factory settings:
AUTO
Block Mode General information on Block Mode
Block Mode contains three elements:
• the block's current operating mode (Actual Mode)
• the modes supported by the block (Permitted Mode):
Analog Input (AI): AUTO, MAN, OOS
Physical Block: AUTO, OOS
Transducer Block: AUTO
• normal operating mode (Normal Mode)
Only the current Block Mode is displayed in the menu.
Generally, you can select from several operating modes in a function
block, while other block types only operate in the AUTO operating
mode for example.
Actual Mode read Displays the current operating mode.
Display:
AUTO