EasyManua.ls Logo

Endress+Hauser Liquiline CM444 - Page 103

Endress+Hauser Liquiline CM444
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Liquiline CM442/CM444/CM448 Operation
Endress+Hauser 103
Xn
Process
balance="Symmetric"
Range of adjustment and
factory setting
Depends on the "Source of
data"
Tolerance range about the setpoint that prevents minor
oscillations about the setpoint if using two-sided control
loops.
XN Low Range of adjustment and
factory setting
Depends on the "Source of
data"
Process balance="Asymmetric"
XN High
XHyst 0.0 to 99.9 %
Factory setting
0.0 %
Width of the hysteresis range of the neutral zone,
relative component of Xn
The graphic illustrates the manipulated variable (with a pure P-controller ) over the control deviation e (set point minus
controlled variable). Very low control deviations are set to zero. Control deviations > X
n
are processed "in the normal
way". Via X
hyst
it is possible to configure a hysteresis to suppress oscillations at the edges.
Clock 0.333 to 100.000 s
Factory setting
1.000 s
Expert setting!
Only change the cycle time of the controller if you know
exactly what you are doing!
Clock < Twu < 0.5(Tn + Tv)
Max Y change rate /s 0.00 to 1.00
Factory setting
0.40
Limits the change of the output variable
Hold behavior Hold=measured value is no longer reliable
Manipulated Variable Options
•Freeze
•Set to zero
Factory setting
Freeze
How should the controller react to a measured value that
is no longer reliable?
Freeze
The manipulated variable is frozen at the current value
Set to zero
Manipulated variable is set to 0 (no dosing)
State Options
•Freeze
Reset
Factory setting
Freeze
Internal controller status
Freeze
No change
Reset
After a hold, the control system starts from scratch, and
settling time takes place again.
Path: Menu/Setup/Additional functions/Controller 1 or Controller 2
Function Options Info

Table of Contents

Other manuals for Endress+Hauser Liquiline CM444