Operation Liquiline CM442/CM444/CM448
108 Endress+Hauser
Defining the cleaning cycle
Path: Menu/Setup/Additional functions/Cleaning/Cleaning 1 ... 4
Function Options Info
Cleaning cycle Options
•Off
•Interval
•Weekly program
Factory setting
Off
Choose from a cleaning routine that is restarted at set
intervals and a user-definable weekly program.
Cleaning cycle= "Interval"
Cleaning interval 00-00:01 to 07-00:00
(DD-hh:mm)
Factory setting
01-00:00
The interval value can be between 1 minute and 7 days.
Example: You have set the value "01-00:00". Each day,
the cleaning cycle starts at the same time you started the
first cleaning cycle.
Cleaning cycle= "Weekly program"
Daily event times 00:00 to 23:59
(HH:MM)
1. "Event time 1 to 6": Define up to 6 times.
You can then choose from these for each
weekday afterwards.
2. For each day of the week, individually choose which
of the 6 times is to be used for a cleaning routine on
this particular day.
In this way you create weekly programs that are
perfectly adapted to suit your process.
Weekdays Monday ... Sunday