EasyManua.ls Logo

Endress+Hauser Liquiline CM444 - Page 37

Endress+Hauser Liquiline CM444
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Liquiline CM442/CM444/CM448 Electrical connection
Endress+Hauser 37
6.5.2 Connection via M12 connector
When using the M12 Y-section, the maximum data transfer rate is limited to 1.5 MBit/s.
For direct wiring, the maximum data transfer rate is 12 MBit/s.
DIP switches on front of module
DIP Factory setting Assignment
1-128 ON Bus address (--> "Commissioning/Communication")
OFF Write protection: "ON" = configuration not possible via the bus, only via local operation
Service OFF Only for service, not to be used by the operator
PROFIBUS DP, Modbus RS485
M12 Y-section Wiring in Y-section Pin assignment in connector and socket
a0016310
Fig. 63: M12 connection
a0016311
Fig. 64: Wiring
a0016312
Fig. 65: Connector (left) and socket (right)
1 P5V, 5 V power supply for external
terminating resistor
2 A (GN), signal RxD/TxD-N
3 P0V, reference potential for P5V
4 B (RD), signal RxD/TxD-P
5 n.c., not connected
*Shield
*=Thread

Table of Contents

Other manuals for Endress+Hauser Liquiline CM444

Related product manuals