10.2.6 Advanced setup
Diagnostics settings
The list of diagnostic messages displayed depends on the path selected. There are device-
specific messages, and messages that depend on what sensor is connected.
Menu/Setup/(General settings or Inputs<Sensor channel>)/Extended setup/Diagnostics settings/Diag.
behavior
Function Options Info
List of diagnostic messages
Select the message to be changed. Only then
can you make the settings for this message.
Diag. code Read only
Diagnostic message Selection
On
Off
Factory setting
Depends on the message
You can deactivate or reactivate a diagnostic
message here.
Deactivating means:
No error message in the measuring mode
No error current at the current output
Error current Selection
On
Off
Factory setting
Depends on the message
Decide whether an error current should be
output at the current output if the diagnostic
message display is activated.
In the event of general device errors, the
error current is output at all the current
outputs. In the event of channel-specific
errors, the error current is only output at
the assigned current output.
Status signal Selection
Maintenance (M)
Out of specification (S)
Function check (C)
Failure (F)
Factory setting
Depends on the message
The messages are divided into different error
categories in accordance with NAMUR NE 107.
Decide whether you want to change a status
signal assignment for your application.
Diag. output Selection
None
Alarm relay
Binary output
Relay 1 to n (depends on
the device version)
Factory setting
None
You can use this function to select a relay output
and/or binary output to which the diagnostic
message should be assigned.
For sensors with the Memosens protocol: Before
being able to assign the message to an output
you must first configure a relay output to
Diagnostics .
(Menu/Setup/Outputs: Assign the Diagnostics
function and set the Operating mode to as
assigned .)
An alarm relay is always available, regardless of the device version. Other relays are optional.
Cleaning program Selection
None
Cleaning 1
Cleaning 2
Cleaning 3
Cleaning 4
Factory setting
None
Decide whether the diagnostic message
should trigger a cleaning program.
You can define the cleaning programs under:
Menu/Setup/Additional functions/Cleaning.
Detail information Read only Here you can find more information on the
diagnostic message and instructions on how to
resolve the problem.