Micropilot FMR56, FMR57
Endress+Hauser 11
Output
Output signal
HART
Signal coding:
FSK ±0.5 mA over current signal
Data transmission rate:
1 200 Bit/s
Galvanic isolation:
Yes
Bluetooth® wireless technology
Device version:
Order code 610 "Accessory mounted", option NF "Bluetooth"
Operation / configuration:
Via the SmartBlue app
Range under reference conditions:
> 10 m (33 ft)
Encryption:
Encrypted communication and password encryption prevent incorrect operation by unauthorized
persons
PROFIBUS PA
Signal coding:
Manchester Bus Powered (MBP)
Data transmission rate:
31.25 kBit/s, Voltage mode
Galvanic isolation:
Yes
FOUNDATION Fieldbus
Signal coding:
Manchester Bus Powered (MBP)
Data transmission rate:
31.25 kBit/s, Voltage mode
Galvanic isolation:
Yes
Switch output
For HART devices, the switch output is available as an option.
Function:
Open collector switch output
Switching behavior:
Binary (conductive or non-conductive), switches when the programmable switch-on point/switch-
off point is reached
Failure mode:
Non-conductive
Electrical connection data:
U = 16 to 35 V
DC
, I = 0 to 40 mA
Internal resistor:
R
I
< 880 Ω
The voltage drop at this internal resistor must be taken into account when planning the
configuration. For example, the resulting voltage at a connected relay must be sufficient to switch
the relay.
Insulation voltages:
Floating, insulation voltage 1 350 V
DC
in relation to power supply and 500 V
AC
ground
Switch point:
User-programmable, separate for switch-on point and switch-off point
Switching delay:
User-programmable in the 0 to 100 s range, separate for switch-on point and switch-off point

Other manuals for Endress+Hauser Micropilot FMR56