Micropilot FMR56, FMR57
Endress+Hauser 33
Installation
Installation conditions Orientation
A
1 2 3
A0016883
Recommended distance A wall - nozzle outer edge: ~ 1/6 of the vessel diameter. However, the
device must not under any circumstances be mounted closer than 20 cm (7.87 in) to the vessel
wall.
If the vessel wall is not smooth (corrugated iron, welding seams, joints, etc.) it is recommended to
maintain the largest possible distance from the wall. Where necessary use an alignment unit to
avoid interference reflections from the vessel wall.
Not in the center (2) as interference can cause signal loss.
Not above the filling curtain (3).
The use of a weather protection cover (1) is recommended to protect the transmitter from direct
sunlight or rain.
In applications with strong dust emissions, the integrated purge air connection can prevent the
antenna from becoming clogged.