Process
Process temperature, process
pressure
The pressure ranges indicated can be reduced by the choice of process connection. The nominal
pressure (PN) indicated on the nameplate refers to a reference temperature of 20 °C, and of
100 °F for ASME flanges. Observe pressure-temperature dependency.
Please refer to the following standards for the pressure values permitted at higher
temperatures:
EN 1092-1: 2001 Tab. 18
With regard to their stability-temperature property, the materials 1.4435 and 1.4404 are
grouped together under 13EO in EN 1092-1 Tab. 18. The chemical composition of the two
materials can be identical.
ASME B 16.5a – 1998 Tab. 2-2.2 F316
ASME B 16.5a – 1998 Tab. 2.3.8 N10276
JIS B 2220
FMR56
p
-40
(-40)
+80
(+176)
0
(+32)
T
p
[°C]
([°F])
[bar] ([psi])
3 (43.5)
-1 (-14.5)
0 (0)
A0023252-EN
 26 FMR56: Permitted range for process temperature and process pressure
Device version Process temperature range Process pressure range
For all versions –40 to +80 °C (–40 to +176 °F) p
rel
= –1 to 3 bar (–14.5 to 43.5 psi)
p
abs
< 4 bar (58 psi)
1)
1) The pressure range may be reduced further if the device has a CRN approval →  81
FMR57
p
-40
(-40)
0
(+32)
T
p
[°C]
([°F])
+400
(+752)
+200
(+392)
1 2
[bar] ([psi])
-1 (-14.5)
0 (0)
16 (580)
A0023253-EN
 27 FMR57: Permitted range for process temperature and process pressure
1 Seal: Viton GLT (feature 090 "Seal", version A6)
2 Seal: graphite (feature 090 "Seal", version D4)