Micropilot FMR56, FMR57
12 Endress+Hauser
• Scan rate:
Corresponds to the measuring cycle
• Signal source / device variables:
• Level linearized
• Distance
• Terminal voltage
• Electronic temperature
• Relative echo amplitude
• Diagnostic values, advanced diagnostic blocks
• Only for active interface measurement
• Number of switch cycles:
Unlimited
Signal on alarm
Depending on the interface, failure information is displayed as follows:
• Current output
• Choice of failure mode (in accordance with NAMUR Recommendation NE 43):
Minimum alarm: 3.6 mA
Maximum alarm (= factory setting): 22 mA
• Failure mode with user-configurable value: 3.59 to 22.5 mA
• Local display
• Status signal (as per NAMUR Recommendation NE 107)
• Plain text display
• Operating tool via digital communication (HART, PROFIBUS PA, FOUNDATION Fieldbus) or
service interface (CDI)
• Status signal (as per NAMUR Recommendation NE 107)
• Plain text display
Linearization
The device's linearization function allows the user to convert the measured value to any length or
volume units. Linearization tables for calculating the volume in cylindrical vessels are
preprogrammed into the device. Other linearization tables of up to 32 value pairs can be entered
manually or semi-automatically.
Galvanic isolation
All circuits for the outputs are galvanically isolated from each other.
Protocol-specific data HART
Manufacturer ID 17 (0x11)
Device type ID 0x1128
HART specification 7.0
Device description files (DTM, DD) Information and files under:
• www.endress.com
• www.fieldcommgroup.org
HART load min. 250 Ω