EasyManua.ls Logo

Endress+Hauser Micropilot FMR56 - Galvanic Isolation

Endress+Hauser Micropilot FMR56
102 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Micropilot FMR56, FMR57
12 Endress+Hauser
Scan rate:
Corresponds to the measuring cycle
Signal source / device variables:
Level linearized
Distance
Terminal voltage
Electronic temperature
Relative echo amplitude
Diagnostic values, advanced diagnostic blocks
Only for active interface measurement
Number of switch cycles:
Unlimited
Signal on alarm
Depending on the interface, failure information is displayed as follows:
Current output
Choice of failure mode (in accordance with NAMUR Recommendation NE 43):
Minimum alarm: 3.6 mA
Maximum alarm (= factory setting): 22 mA
Failure mode with user-configurable value: 3.59 to 22.5 mA
Local display
Status signal (as per NAMUR Recommendation NE 107)
Plain text display
Operating tool via digital communication (HART, PROFIBUS PA, FOUNDATION Fieldbus) or
service interface (CDI)
Status signal (as per NAMUR Recommendation NE 107)
Plain text display
Linearization
The device's linearization function allows the user to convert the measured value to any length or
volume units. Linearization tables for calculating the volume in cylindrical vessels are
preprogrammed into the device. Other linearization tables of up to 32 value pairs can be entered
manually or semi-automatically.
Galvanic isolation
All circuits for the outputs are galvanically isolated from each other.
Protocol-specific data HART
Manufacturer ID 17 (0x11)
Device type ID 0x1128
HART specification 7.0
Device description files (DTM, DD) Information and files under:
www.endress.com
www.fieldcommgroup.org
HART load min. 250 Ω

Other manuals for Endress+Hauser Micropilot FMR56

Related product manuals