Micropilot FMR56, FMR57
8 Endress+Hauser
Output
The Micropilot is configured by entering the empty distance "E" (= zero), the full distance "F" (= span)
and application parameters which automatically adapt the device to the process conditions. For
models with a current output, the factory adjustment for zero point "E" and span "F" is 4 mA and 20
mA. For digital outputs and the display module, the factory adjustment for zero point "E" and span "F"
is 0 % and 100 %.
A linearization function with max. 32 points, based on a table entered either manually or semi-
automatically, can be activated locally or remotely. This function provides a measurement in
engineering units and a linear output signal for spherical and horizontal cylindrical vessels and
vessels with a conical outlet.
Product life cycle
Planning
Universal measuring principle
Measurement is independent of product properties
Hardware and software developed according to SIL IEC 61508
Procurement
As the global market leader in level measurement, Endress+Hauser guarantees the security of
your investment
Worldwide support and service
Installation
No special tools are required
Protection against reverse polarity
Modern, detachable terminals
Main electronics protected by a separate connection compartment
Commissioning
Fast, menu-guided commissioning in only a few steps onsite or from the control room
Plain text display in local language reduces the risk of error or confusion
Direct local access to all parameters
Printed Brief Operating Instructions in the device onsite
Operation
Multi-echo tracking: Reliable measurement thanks to self-learning echo search algorithms taking
into account the short-term and long-term history and plausibility of the detected signals to
suppress interference echoes.
In accordance with NAMUR NE107
Maintenance
HistoROM: Data backup for device settings and measured values
Exact device and process diagnostics to assist fast decisions with clear information regarding
remedial action
Intuitive, menu-guided operating concept in local language saves costs for training, maintenance
and operation
Cover of the electronics compartment can also be opened in the hazardous area